6.2.5 Reset Status

@Description

Read the reset status of module at specified address to check
whether if it has been reset since the last reset status
command was issued to the module.

@Syntax

$(Addr)5<CR>

$

Command leading code.

(Addr) Address

ID.

5

Reset Status Command.

@Response

!(Addr)(Status)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(Status)

0 : It has not been reset since the last reset
status command was issued.
1 : It has been reset since the last reset
status command was issued.

@Example

User command:

$185<CR>

Response:

!180<CR>

Status is 0 means this digital I/O module has not been reset,
since the last reset status command was issued.

(601x,602x,605x,60
6x,6080,6531)