9.2 How to Calibrate the Analog Output Modules ?

What do you need to do calibration ?

1.

One 5 1/2 digit multimeter.

2.

A resistor 250

Ω (Accurary is 0.01 %).

3.

NuDAM Aministration Utility.

Calibration Procedure

1.

Select output range to 0 ~20 mA or 4~20 mA.

2.

Put the resistor 250

Ω to the NuDAM-6021 (+ IOUT (Pin.1) and -IOUT

(Pin.2)).

3. Put 5 1/2 digit multimeter to measure + IOUT (Pin.1) and -IOUT

(Pin.2) .

4. Send the “Analog Data Output #(Addr)(OutData)” command with

output value is 4 mA. For example if the address is 0x03 then

the

command is

#0304.000.

5. Use

Trim calibration $(Addr)3(Counts)” command to adjust until the

output value to 1 V (4 mA).

6. Send

4mA Calibration $(Addr)0” command to the analog output

module to complete the 4 mA calibration.

7. Send the “Analog Data Output #(Addr)(OutData)” command with

output value is 20 mA. For example if the address is 0x03 then the

command is

#0320.000

8. Use

Trim calibration $(Addr)3(Counts)” command to adjust until the

output value to 5 V (20 mA).

9. Send

20mA Calibration $(Addr)1” command to the analog output

module to complete the 20 mA calibration.