6.7.31 Set Digital Output Values
@Description
Set the value (ON or OFF) of the 2 channel digital outputs.
@Syntax
@(Addr)DO(DoData)<CR>
@
Command leading code.
(Addr) Address
ID
DO
Set digital data output command code.
(DoData)
00: DO0 is OFF, DO1 is OFF
01: DO0 is ON, DO1 is OFF
02: DO0 is OFF, DO1 is ON
03: DO0 is ON, DO1 is ON
@Response
!(Addr)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
@30DO01<CR>
Response:
!30<CR>
Item Meaning
Description
@
(Leading Code)
Command leading code.
30
(Addr)
Address ID is 30H.
DO
Set digital data output.
01
(D0Data)
DO0 is ON, DO1 is OFF
(6080)