ADLINK ND-6067 User Manual

Page 173

Advertising
background image

171

6.4.8 Last Value Readback

@Description

Return the latest analog output value which is set by “Analog
Data Out” command. If the analog output module never
execute the “Analog Data Out” command then it return the
start-up output value. (only 6021)

@Syntax

$(Addr)6<CR> (only 6021)

$(Addr)6(Port)<CR> (6024 Only)

$

Command leading code. (1-character)

(Addr)

Address ID. (2-character)

6

Function code of last value readback.
(1-character)

(Port)

Port A, B, C or D.

@Response

!(Addr)(Data)<CR>

or

?(Addr)<CR>

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(Data)

The current analog output value, the data format
depends on module configuration.

@Example

User command:

$086<CR>

Response:

!0802.000<CR>

This analog output module return the latest output value is 2.000 mA at
address 08H, if data format is engineering units and the signal range is
0~20mA.

(602x)

Advertising