Therefore, to configure the brand-new NuDAM before using is
necessary to avoid conflicting address. The baud rate may also
be changed according to user‘s requirements.
The initialization procedures of a brand-new NuDAM are shown
in the following sections. The procedures are applicable for
initializing NuDAM-6013, NuDAM-6017, NuDAM-6018
NuDAM-6021, NuDAM-6024, NuDAM-6050, NuDAM-6052
NuDAM-6053, NuDAM-6054, NuDAM-6056, NuDAM-6060
NuDAM-6063, NuDAM-6067, NuDAM-6080, and NuDAM-6531.

Default State

The NuDAM modules must be set at Default State when you
want to change the default settings, including the ID address,
baud rate, check-sum status etc. All NuDAM modules have an
special pin labeled as DEFAULT*. The module will be in Default
State
if the Default

*

1

pin is shorted to ground and then power on

module again. Under Default state, the default configuration is
set as following:

Address ID is 00.

Baud rate is 9600 bps.

Check-sum disable.

Watchdog timer is disable.


Therefore, the configuration of the host and the module can be
easily set identically and initializing a module will be possible no
matter what configuration is set under operating state.

Initialization Equipments

• Host computer with an RS-232 port.
• An installed RS-485 module (NuDAM-6520) with 9600 baud

rate.

• The brand new NuDAM module
• Power supply (+10 V

DC

to +30 V

DC

) for NuDAM modules

• Administration utility software

Note: Never Connect the DRFAULT* pin to Vs or power source

just left it open or wired to GND.