Initialization Procedure

1. Power off the host computer and the installed NuDAM-6520.

Be sure of the baud rate of the NuDAM-6520 is 9600 bps.

2. Connect a brand-new NuDAM module with the RS-485. Set

the module in Default State by shorting the DEFAULT* pin.
Refer to Figure 7-1 for detailed wiring.

3. Power on the host computer.
4. Power on the power supply for NuDAM modules.
5. Use the NuDAM Administration utility to configure the

address ID, Baud rate and check-sum status of the module.

Initialization Wiring
















Figure 7-1 Layout for Initialization the NuDAM module