ADLINK ND-6067 User Manual

Page 170

Advertising
background image

168

6.4.5 4mA Offset Calibration

@Description

Stores the current output value as 4 mA reference at the
specified analog output module.(only 6021)

@Syntax

$(Addr)0<CR>

$

Command leading code

(Addr) Address

ID

0 Command

Code

@Response

!(Addr)<CR>
or
?(Addr)<CR>

!

Command is valid.

?

Command is invalid or no synchronized sampling
command was issued.

(Addr) Address

ID.

@Example

User command:

$060<CR>

Response:

!06<CR>

To perform the 4 mA calibartion for analog output module at address
06H.

Note : Analog output module should be trimmed to the correct

value by “Trim Calibration” command before to execute
“4 mA Calibration”. Refers to Chapter 5 “Analog Output
Calibration” for details.

(6021)

Advertising
This manual is related to the following products: