ADLINK ND-6067 User Manual

Page 259

Advertising
background image

257

Code

Input Range

Thermocouple

Data

Format

Maximum

Minimum

Displayed

Resolution

0E

J (0

°C to 760°C)

Eng. Units

+760.00

+000.00

0.01

°C

0F

K (0

°C to 1000°C)

Eng. Units

+1000.0

+0000.0

0.1

°C

10

T (-100

°Cto400°C)

Eng. Units

+400.00

-100.00

0.01

°C

11

E (0

°C to 1000°C)

Eng. Units

+1000.0

+0000.0

0.1

°C

12

R (500

°C to 1750°C)

Eng. Units

+1750.0

+0500.0

0.1

°C

13

S (500

°C to 1750°C)

Eng. Units

+1750.0

+0500.0

0.1

°C

14

B (500

°C to 1800°C)

Eng. Units

+1800.0

+0500.0

0.1

°C

15

N (-270

°C to 1300°C)

Eng. Units

+1300.0

-0270.0

0.1

°C

16

C (0

°C to 2320°C)

Eng. Units

+2320.0

+0000.0

0.1

°C

Table 8-3 Thermocouple Type ,Temperature Range and resolution <ND-6018>

Code

Output

Range

Data

Format

Maximum

Value

Minimum

Value

Output

Resolutio

n

30

0 to 20 mA

Eng. Units

20.000

00.000

4.88

μA

31

4 to 20 mA

Eng. Units

20.000

04.000

4.88

μA

32

0 to 10 V

Eng. Units

10.000 00.000

2.442

mV

Table 8-4 Analog Output Range and resolution<ND-6021,ND-6024>

‹ Example 1:

Input Range is

±5 V

Input is -1.37 Volts

engineering units: -1.3700<CR>

‹ Example 2:

Input Range is

±10 V

Input is +3.653 Volts

engineering units: +03.653<CR>

‹ Example 3:

Input Range is Type K thermocouple (range 0

°C to 1000°C)

Input is 406.5

°C

engineering units: +0406.5<CR>

‹ Example 4:

Advertising