Input Range is Type T thermocouple (range -100

°C to 400°C)

Input is -50.5

°C

engineering units:

-

050.50<CR>

‹ Example 5:

Output range is 0 to 20 mA

Output value is +5.678 mA

The data value should be : 05.678<CR>

‹ Example 6:

Output range is 0 to 10 V

Output value is +2.345 V

The data value should be : 02.345<CR>

8.2 Percent of FSR (Full Scale Range)


• Data format bit 1 and 0 set to 01 is percent of FSR
• This data format including three components
1. sign (+ or - )
2. digits
3. decimal point
• Data is sign (+ or - ) followed with 5-digits and a decimal

point

• It does not exceed 7-characters. Data string of analog

output modules is fixed length of 6 characters. The value is
composed of five decimal digits with a decimal fixed point.

• Analog input modules maximum resolution is 0.01%, and

the decimal point is fixed.Analog output modules maximum
resolution is 0.2%.

• Data is the ratio of input signal to the value of full scale range

The different analog input/output ranges have different
resolutions. Refer to Table 8-5 ,Table 8-6 and Table 8-7 for
details.