Therefore, the communication between the host and the module can be easily
set up as the same configuration, the initialization of a module is possible no
matter what configuration is set under operating state

Initialization Equipments

Host computer with a RS-232 port.

An installed RS-485 module (ND-6520 or ND-6530) with 9600 baud rate.

The brand new ND-6531

Power supply (+10 to +30 V

DC

) for NuDAM modules

Administration utility software

Note : Never Connect the DRFAULT* pin to Vs or power source just left it

open or wired to GND.

Initialization Procedure

1. Power off the host computer and the installed ND-6520 or ND-6530. Be sure

that the baud rate of the ND-6520 or ND-6530 is 9600 bps.

2. Connect a brand new NuDAM module with the RS-485. Set the module in

Default State by shorting the DEFAULT* pin. Refer to Figure 2-12 for detailed
wiring.

3. Power on the host computer.

4. Power on the power supply for NuDAM modules.

5. Use the NuDAM Administrating utility to configure the address ID, Baud rate

and check-sum status of the module.