6.5.1 Synchronized Sampling

@Description

Synchronized all modules to sample input values and stored
the values in the module’s register at the same time and use
“Read Synchronized Data” command to read the data and
process it one by one.
For digital I/O module, this command is only available to
modules involving the digital input function, such as
NuDAM-6050, NuDAM-6052, NuDAM-6053, NuDAM-6054,
NuDAM-6058 and NuDAM-6060.

@Syntax

#**<CR>

#

Command leading code.

**

Synchronized sampling command

@Response

Note : Synchronized sampling command has NO response.

@Example

User command:

#**<CR>

Synchronized sampling command has no response

.

(6050, 6052, 6053,

6054,6058, 6060)