6.2.1 Set Configuration

@Description

Configure the basic setting of NuDAM, including the address
ID, input range, baud rate, and data format. The new
configuration will be available after executing the command.

@Syntax

%(OldAddr)(NewAddr)(InputRange/OutputRange/TypeCod

e)(BaudRate)(DataFormat/

CheckSumFlag

/DataFlag)<CR>

%

Command leading code. (1-character)

(OldAddr)

NuDAM module original address ID. The default address ID
of a brand new module is 01. The value range of address ID
is 00 to FF in hexadecimal.
(2-character)

(NewAddr)

New address ID, if you don’t want to change address ID, let
new address ID equals to the old one. (2-character)

(InputRange)

Define analog input range, refers to Table 6-1
for details. (2-character)

601x

(OutputRange) Define

analog output range, refers to Table 6-2

for details. (2-character)

602x

(TypeCode)

Type Code is fixed 40H for Digital I/O modules.
(2-character)

605x,606x,
6531

Type Code represents the input mode.
(2-character)
50: counter input mode
51: frequency input mode

6080

(BaudRate)

Define communication baud rate, refers to Table 6-3 for
details. (2-character)

(DataFormat) Define

checksum, integration time and output

data format, refers to Figure 6-1 for details.
(2-character)

601x

Define checksum, integration time and output
data format, refers to Figure 6-2 for details.
(2-character)

602x

(CheckSumFlag)

Define check-sum status, refer to Figure 6-3
for details. (2-character)

605x

Define check-sum status, refer to Figure 6-4
for details. (2-character)

6080

(DataFlag)

Define check-sum status, refer to Table 6-4 for
details. (4-character, WXYZ) WX is for module
system setting. YZ is for RS-232 configuration.

6531

(601x,602x,605x,606x,

6080,6531)