5.2 Overview of ND-6052

ND-6052 provides 8 isolated digital input channels. Six of the input channels
are differential type and two of them are single-ended with common ground.
The isolation voltage is up to 5000 Vrms. It is suitable to use ND-6052 in
industrial environment with high voltage electric shock.

5.2.1 Features of ND-6052

z

8 bits isolated input

z

5000 Vrms isolation voltage

z

Programmable host watchdog timer for host failure protection

z

Internal watchdog timer for device failure protection

z

Easy programming by software

z

Easy installation and wiring

5.2.2 Specifications of ND-6052

‹ Interface

Interface : RS-485, 2 wires

Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K,

115.2K

‹ Input

Channel number : 6 differential channels, 2 single ended

Logical level 0 : +1V Max.

Logical level 1: +3.5V ~ +24V

‹ Watchdog Function

Module internal watchdog timer : 150ms

Power failure threshold : 4.65 V

Safe value : 8 output channels

Host programmable watchdog :100 ms ~ 25.5 sec

‹ Power

Power supply : +10V to +30V

Current consumption : 0.264 W