6.5.3 Digital Output

@Description

Set digital output channel value at specified address. This
command is only available to modules involving the digital
output function.

@Syntax

#(Addr)(ChannelNo)(OutData)<CR>

#(Addr)T(OutDataH)(OutDataL)<CR> (6056 only)

#(Addr)T(OutDataA)(OutDataB)(OutDataC)<CR> (6058 only)

#(Addr)(Port)(OutData1)<CR> (6056, 6058 only)

#

Command leading code. (1-character)

(Addr)

Address ID (2-character)

T

Set value to all channels

(ChannelNo)

00 : Set value to all channels
1X : Set value to single channel
First character is 1, Second character is
channel number. (2-character)

(OutData)

Set value to all channels :
Each bit is mapping to each channel number
Set value to single channel :
First character is 0, second character is set to value 0
or 1. (2-character)

(OutDataH)

Each bit is mapping to each channel number from 14
to 8. (2-character)

(OutDataL)

Each bit is mapping to each channel number from 7 to
0. (2-character)

(OutDataA)

Output data for port A. Each bit is mapping to each
channel number from 7 to 0. (2-character)

(OutDataB)

Output data for port B. Each bit is mapping to each
channel number from 7 to 0. (2-character)

(OutDataC)

Output data for port C. Each bit is mapping to each
channel number from 7 to 0. (2-character)

(Port)

Set value to indivisual port
0H: for 6056 channel 14 to 8
0L: for 6056 channel 7 to 0
0A: for 6058 port A
0B: for 6058 port B
0C: for 6058 port C (2-character)

(6050,6056,6058,

6060,6063,6067)

Advertising