Programming 5 - 18

b5-10 PI Output Gain Setting

Setting Range:

0.0 to 25.0

Factory Default: 1.0

Applies a multiplier to the output of the PI function. Using the gain can be helpful when the PI function is used to trim the
Speed Command. Increasing b5-10 causes the PI function to have a greater regulating affect on the speed command.

b5-11 PI Reverse Selection

Parameter b5-11 determines whether reverse operation is allowed while using PI control (b5-01

≠0). The factory default setting

will not allow the Drive to run in reverse. This parameter does not need to be changed from factory default for a majority of
HVAC applications. (Refer also to b5-09).

b5-12 PI Feedback Reference Missing Detection Selection

Loss of feedback can cause problems to a PI application. The Drive can be programmed to turn on a digital output whenever a
loss of feedback occurs. Feedback Loss Detection is turned on by b5-12. When b5-12= “1: Alarm”, the Drive acknowledges
the loss of feedback without stopping or turning on the fault output (MA-MB). If b5-12= “2: Fault”, the Drive coasts to a stop
and turns on the fault output if the feedback is determined to be lost.

b5-13 PI Feedback Loss Detection Level

Setting Range:

0 to 100%

Factory Default: 0%

b5-14 PI Feedback Loss Detection Time

Setting Range:

0.0 to 25.0 Seconds

Factory Default: 1.0 Seconds

The Drive interprets feedback loss whenever the feedback signal drops below the value of b5-13 and stays below that level for
at least the time set into b5-14. See Figure below for timing details.

Fig. 17 Loss of PI Feedback Feature

Setting

Description

0

0 Limit (factory default)

1

Reverse

Setting

Description

0

Disabled (factory default)

1

Alarm

2

Fault

Measured
Feedback

T

t

Feedback

Loss Output

T

b5-13

T = b5-14

Feedback

Loss Digital Output

ON (CLOSED)

OFF (OPEN)

TIME