Yaskawa P7 Drive User Manual User Manual

Page 83

Advertising
background image

Start Up 4 - 9

21. Check the signal for proper polarity. Observe if the speed command can achieve the minimum and maximum speeds

desired. If not, perform the following:

For 0-10Vdc input (Terminal A1)

1.

With no input, adjust Bias (H3-03 setting) until an output of “0.0 Hz” is obtained.

2.

With full-scale input, adjust Gain (H3-02 setting) until an output of “60.0 Hz” (or other desired maximum
frequency) is obtained.

For 4-20mA input (Terminal A2)

1.

With 4mA input, adjust Bias (H3-11 setting) until an output of “0.0 Hz” is obtained.

2. With 20 mA input, adjust Gain (H3-10 setting) until an output of “60.0 Hz”

(or other desired maximum frequency) is obtained.

THIS COMPLETES THE DRIVE START UP PROCEDURE.