Programming 5 - 45

The setting of parameter L5-02 determines whether the fault output (MA-MB) will be closed during an auto restart attempt.
The setting of L5-02 can be important when interfacing the Drive with other equipment.

The following faults will allow the Auto Restart function to initiate:

•

OC (Overcurrent)

•

LF (Output Open Phase)

•

PF (Input Phase Loss)

•

PUF (DC Bus Fuse)

•

OL1 (Motor Overload)

•

OL3 (Overtorque)

•

OL2 (Drive Overload)

•

OV (DC Bus Overvoltage)

•

GF (Ground Fault)

•

UV1 (DC Bus Undervoltage)

•

OH1 (Overheat)

In order for auto restart after a UV1 fault, Momentary Power Loss Ride-thru must be enabled (L2-01= “1: PwrL Ride Thru t”,
or “2: CPU Power Active”). Setting H2-01 or H2-02 equal to “1E” configures a digital output as “Restart Enabled” to signal if
an impending auto restart is possible.