Programming 5 - 13 – Yaskawa P7 Drive User Manual User Manual

Page 97

Advertising
background image

Programming 5 - 13

Fig. 12 Speed Search (Current Detection Method) at Startup

Fig. 13 Speed Search (Current Detection Method) after momentary power loss where the power loss

time is less than the minimum baseblock time

Fig. 14 Speed Search (Current Detection Method) after momentary power loss where the power loss

time exceeds the minimum baseblock time

IMPORTANT

If an OC fault occurs when Speed Search is attempted after power loss recovery, increase the setting of L2-03.

Speed Search Settings and Methods

Setting of

b3-01

Automatic Speed Search

for all RUN commands

Automatic Speed Search after

momentary power loss and

baseblock

Speed Search Used for Run with

programmed multi-function

input

0

No

Yes - Speed Estimation

Yes - Speed Estimation

1

Yes - Speed Estimation

Yes - Speed Estimation

Yes - Speed Estimation

2

No

Yes - Current Detection

Yes - Current Detection

3

Yes - Current Detection

Yes - Current Detection

Yes - Current Detection

Run command

Output frequency

Output current

OFF

ON

b3-02

Deceleration time set in b3-03

Set frequency
reference

Minimum baseblock time
(L2-03)

Maximum output
frequency or
set frequency

* Lower limit is set using Speed Search Time (b3-05).

*

Search Delay Time (b3-05).

Speed search current level

AC power supply

Output frequency

Output current

OFF

ON

Output frequency before power loss

Set frequency
reference

Minimum baseblock time (L2-03)

*1 Baseblock time may be reduced by the output frequency
immediately before baseblock.
*2 After AC power supply recovery, motor waits for the minimum
Speed Search Wait Time (b2-03).

Deceleration
time set in b3-03

b3-02

speed search operating current

*2

*1

b3-05

AC power supply

Output frequency

Output current

OFF

ON

Output frequency before power loss

Set frequency
reference

Minimum baseblock time
(L2-03)

Deceleration speed set in b3-03

b3-02

Speed search operating time

Speed search wait time (b3-05)

Deceleration time set in b3-03

Advertising