Parameters a - 19, Pwrloss ridethru, Stall prevention – Yaskawa P7 Drive User Manual User Manual

Page 193: Table 1, Parameter list (continued

Advertising
background image

Parameters A - 19

PwrLoss Ridethru

L2-01

Momentary Power Loss Detection
Selection
PwrL Selection

Enables and disables the momentary power loss
function.
0: Disabled - Drive trips on (UV1) fault when power is

lost.

1: PwrL Ride Thru t - Drive will restart if power returns

within the time set in L2-02.*

2: CPU Power Active - Drive will restart if power

returns prior to internal power supply shut down.*

* In order for a restart to occur, the run command must

be maintained throughout the ride thru period.

0 to 2

2

Programming

L2-02

Momentary Power Loss Ride-thru
Time
PwrL Ridethru t

Determines the power loss ride-thru time. This value is
dependent on the capacity of the drive. Only effective
when L2-01 = 1.

0.0 to

25.5sec

kVA

Dependent

Programming

L2-03

Momentary Power Loss Mini-
mum Base Block Time
PwrL Baseblock t

Used to allow the residual motor voltage to decay
before the drive output turns back on. After a power
loss, if L2-03 is greater than L2-02, operation resumes
after the time set in L2-03.

0.1 to 5.0sec

kVA

Dependent

Programming

L2-04

Momentary Power Loss Voltage
Recovery Ramp Time
PwrL V/F Ramp t

The time it takes the output voltage to return to the
preset V/f pattern after speed search (current detection
mode) is complete.

0.0 to 5.0sec

kVA

Dependent

Programming

L2-05

Undervoltage Detection
Level
PUV Det Level

Sets the drive's DC Bus undervoltage trip level. If this is
set lower than the factory setting, additional AC input
reactance or DC bus reactance may be necessary.

Voltage

Class

Dependent

Voltage

Class

Dependent

Programming

Stall Prevention

L3-01

Stall Prevention Selection During
Accel
StallP Accel Sel

0: Disabled (Motor accelerates at active acceleration,

C1-01 or C1-03. The motor may stall if load is too
heavy or accel time is too short).

1: General Purpose (When output current exceeds L3-

02 level, acceleration stops. It starts to accelerate at
current value recovery).

2: Intelligent (The active acceleration rate, C1-01 or

C1-02, is ignored. Acceleration is completed in the
shortest amount of time w/o exceeding the current
value set in L3-02).

0 to 2

1

Programming

L3-02

Stall Prevention Level During
Accel
StallP Accel Lvl

This function is enabled when L3-01 is “1” or “2”.
Drive rated current is 100%. Decrease the set value if
stalling occurs at factory setting.

0 to 200

120%

Programming

L3-04

Stall Prevention Selection During
Decel
StallP Decel Sel

0: Disabled (The drive decelerates at the active
deceleration rate, C1-02 or C1-04. If the load is too

large or the deceleration time is too short, an OV fault
may occur).

1: General Purpose (The drive decelerates at the active

deceleration rate, C1-02 or C1-04, but if the main

circuit DC bus voltage reaches the stall prevention

level the output frequency will clamp. Deceleration
will continue once the DC bus level drops below the
stall prevention level).

2: Intelligent (The active deceleration rate is ignored

and the drive decelerates as fast as possible w/o

hitting OV fault level).

0 to 3

1

Programming

L3-05

Stall Prevention Selection During
Run
StallP Run Sel

0: Disabled (Drive runs a set frequency). A heavy load

may cause the drive to trip on an OC fault.

1: Decel Time 1 (In order to avoid stalling during heavy

loading, the drive will start to decelerate at Decel
time 1 (C1-02) if the output current exceeds the level
set by L3-06. Once the current level drops below the
L3-06 level the drive will accelerate back to its set
frequency at the active acceleration rate).

2: Decel Time 2 (Same as setting 1 except the drive

decelerates at Decel Time 2 (C1-04).

For 6Hz or less frequency, stall prevention function

during run is disabled regardless of L3-05 set.

0 to 2

1

Programming

L3-06

Stall Prevention Level During
Running
StallP Run Level

This function is enabled when L3-05 is “1” or “2”.
Drive rated current is set as 100%.
Normally, changing the setting is not required.
Decrease the set value if stalling occurs at factory
setting.

30 to 200

120%

Programming

Table 1:

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting