Programming 5 - 20

In order to use parameter b5-19 as the PI Setpoint, set parameter b5-18= “1: Enabled”. If b5-18= “0: Disabled” the PI Setpoint
will either be:

Modbus Register 06H (If Register 0FH bit 1 is high)

The active speed command (i.e. Determined by the setting of b1-01). See Table 1 “Setpoint Options”

b5-19 PI Setpoint Value

Setting Range:

0.00 to 100.00%

Factory Default: 0.00%

Parameter b5-19 is for a PI Setpoint value. When b5-18= “1: Enabled”, the value of b5-19 will take precedent over any other
PI setpoint unless the Drive is set up for Differential Feedback, in which case, b5-18 and b5-19 have no affect on the PI
function.

b5-20 PI Setpoint Display Scaling

The PI Setpoint Display Scaling value (b5-20) is a scaling factor that is applied to the monitor display for both the PI Setpoint
(U1-38) and the PI Feedback (U1-24).

If the monitors seem more natural in terms of percentage, set b5-20= 1. If the monitors are easier to work with when
displaying the equivalent synchronous RPM, set b5-20= [the number of motor poles].

If another engineered unit, such a fpm or cfm, is desired, set b5-20= xxxxx where

X X X X X

Digit 5 Digit 4 Digit 3 Digit 2 Digit 1

Digits 1 through 4 set the desired number to be displayed at 100% speed.
Digit 5 determines the number of decimal places

If Digit 5 = 0 number format is XXXX
If Digit 5 = 1 number format is XXX.X
If Digit 5 = 2 number format is XX.XX
If Digit 5 = 3 number format is X.XXX

Setting

Description

0

Hz (factory default)

1

%

3

RPM (Synchronous)

3

Engineering Units

Table 2 PI Setpoint Display Scaling Options

If b5-20 is:

U1-24 and U1-38

Display Increments.

0

0.01 Hz

1

0.00%

2 through 39

(enter the # of motor poles)

0 RPM

40 through 39999

Engineering Units