Programming 5 - 35, H3-08 terminal a2 signal level – Yaskawa P7 Drive User Manual User Manual

Page 119

Advertising
background image

Programming 5 - 35

H3-08 Terminal A2 Signal Level

The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2
analog input. The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The Drive also has a
DIP switch (S1) on the removable terminal board that must be set for the proper reference signal into the A2 analog input. The
S1-2 dipswitch setting determines the internal resistance of the A2 input while parameter H3-08 determines how the Drive
interprets the measured signal.

Fig. 27 DIP Switch S1

Setting

Description

0

0 - 10VDC

2

4 - 20mA (Default)

Table 4 DIP Switch S1

Name

Function

Setting

S1-1

RS-485 and RS-422 terminating
resistance

OFF: No terminating resistance
ON: Terminating resistance of 110

Ω

S1-2

Input signal for analog input A2

OFF: 0 to 10 V (internal resistance: 20 k

Ω)

ON: 4 to 20 mA (internal resistance: 250

Ω) (Default)

S1

O

1

Terminating
resistance

DIP Switch S1-1 located on
terminal board.

2

1

Advertising