Maintenance 7 - 2

Periodic Inspection

Check the following items during periodic maintenance.

The motor should not be vibrating or making unusual noises.

There should be no abnormal heat generation from the Drive or motor.

The ambient temperature should be within the Drive specification of -10

°C to 40°C (14°F to 104°F).

The output current value shown in parameter U1-03 should not be higher than the motor rated current for an extended period
of time.

The cooling fan in the Drive should be operating normally.

Always turn OFF the input power before beginning inspection. Confirm that the digital operator indicators on the front cover
have all turned OFF, and then wait an additional five minutes before beginning the inspection. Be sure not to touch terminals
immediately after the power has been turned off. Doing so can result in electric shock. Please refer to Warnings on page i.

Apply power to the Drive and conduct the following inspection.

WARNING

Prior to removing any protective cover or wiring any part of the Drive, remove all power sources, including
main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before
removing any cover. The charge lamp located within the Drive should be off prior to working inside. Even if
the charge lamp is off, one must measure the AC input, output, and DC Bus potential to insure safe levels
prior to resuming work. Failure to adhere to this warning may result in personal injury or death.

Table 7.1 Periodic Inspections With no Power Applied

Item

Inspection

Corrective Action

External terminals,

mounting bolts,
connectors, etc.

Are all screws and bolts tight?

Tighten loose screws and bolts firmly.

Are connectors tight?

Reconnect the loose connectors.

Cooling fins

Are the fins dirty or dusty?

Clean off any dirt and dust with an air gun using

clean and dry air at a pressure between 55-85 psi.

Control PCB

Terminal PCB

Power PCB

Gate Drive PCBs

Is there any conductive dirt or oil mist on the

PCBs?

Clean off any dirt and dust with an air gun using

clean and dry air at a pressure between 55-85 psi.

Replace the boards if they cannot be made clean.

Input Diodes

IPMs

Output Transistors

Is there any conductive dirt or oil mist on the

modules or components?

Clean off any dirt and dust with an air gun using

clean and dry air at a pressure between 55-85 psi.

DC bus capacitors

Are there any irregularities, such as

discoloration or odor?

Replace the capacitors or Drive.

Table 7.2 Periodic Inspections With Power Applied

Item

Inspection

Corrective Action

Cooling fan(s)

Is there any abnormal noise or vibration, or has

the total operating time exceeded 20,000

hours.Check U1-40 for elapsed cooling fan

operation time.

Replace Cooling Fan