Parameters A - 17

Table 1:

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

Analog Outputs

H4-01

Terminal FM Monitor Selection
Terminal FM Sel

Selects which monitor will be output on terminals FM
and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary

current)

20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * FM gain setting
(H4-02).

1 to 53

2

Programming

H4-02

Terminal FM Gain Setting
Terminal FM Gain

Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 100% output.

0.0 to

1000.0

100.0%

Programming

H4-03

Terminal FM Bias Setting
Terminal FM Bias

Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 0% output.

–110.0 to

110.0

0.0%

Programming

H4-04

Terminal AM Monitor Selection
Terminal AM Sel

Selects which monitor will be output on terminals AM
and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary

current)

20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * AM gain setting
(H4-05).

1 to 53

8

Programming

H4-05

Terminal AM Gain Setting
Terminal AM Gain

Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 100% output.

0.0 to

1000.0

50.0%

Programming

H4-06

Terminal AM Bias Setting
Terminal AM Bias

Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 0% output.

–110.0 to

110.0

0.0%

Programming

H4-07

Terminal FM Signal Level
Selection
AO Level Select1

0: 0 - 10 VDC
2: 4-20 mA*

0 or 2

0

Programming

H4-08

Terminal AM Signal Level
Selection
AO Level Select2

0: 0 - 10 VDC
2: 4-20 mA*
* An analog output of 4 - 20 mA can not be used with
the standard terminal board. Therefore an optional
terminal board (with shunt connector CN15) is needed.

0 or 2

0

Programming