Parameters a - 9, Carrier freq, Preset reference (speeds) – Yaskawa P7 Drive User Manual User Manual

Page 183: Reference limits, Jump frequencies, Table 1: parameter list (continued)

Advertising
background image

Parameters A - 9

Carrier Freq

C6-01

Normal Duty Selection
Normal Duty Sel

1: Normal Duty 1
2: Normal Duty 2

1 or 2

2

Programming

C6-02

Carrier Frequency Selection
CarrierFreq Sel

Carrier frequency sets the number of pulses per second of the out-
put voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)

0 to F

kVA

Dependent

Programming

C6-03

Carrier Frequency Upper
Limit
CarrierFreq Max

Maximum carrier frequency allowed when C6-02 = F.

kVA

Dependent

kVA

Dependent

Programming

C6-04

Carrier Frequency Lower
Limit
CarrierFreq Min

Minimum carrier frequency allowed when C6-02 = F.

kVA

Dependent

kVA

Dependent

Programming

C6-05

Carrier Frequency Propor-
tional Gain
CarrierFreq Gain

Sets the relationship of output frequency to carrier frequency when
C6-02 = F.

0 to 99

0

Programming

Preset Reference (Speeds)

d1-01

Frequency Reference 1
Reference 1

Digital preset speed command 1. Used when b1-01 = 0. Setting
units are affected by o1-03.

0.00 to

E1-04

Value

0.00Hz

Programming

d1-02

Frequency Reference 2
Reference 2

Digital preset speed command 2. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-03

Frequency Reference 3
Reference 3

Digital preset speed command 3. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-04

Frequency Reference 4
Reference 4

Digital preset speed command 4. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-17

Jog Frequency Reference
Jog Reference

Speed command used when a jog is selected via multi-function
input terminals. Setting units are affected by o1-03.

0.00 to

E1-04

Value

6.00Hz

Programming

Reference Limits

d2-01

Frequency Reference Upper
Limit
Ref Upper Limit

Determines maximum speed command, set as a percentage of
parameter E1-04. If speed command is above this value, actual
drive speed will be limited to this value. This parameter applies to
all speed command sources.

0.0 to 110.0

100.0%

Quick Setting

d2-02

Frequency Reference Lower
Limit
Ref Lower Limit

Determines minimum speed command, set as a percentage of
parameter E1-04. If speed command is below this value, actual
drive speed will be set to this value. This parameter applies to all
speed command sources.

0.0 to 110.0

0.0%

Quick Setting

d2-03

Master Speed Reference
Lower Limit
Ref1 Lower Limit

Determines the minimum speed command, set as a percentage of
parameter E1-04. If speed command is below this value, actual
drive speed will be set to this value. This parameter only applies to
analog inputs A1 and A2.

0.0 to 110.0

0.0%

Programming

Jump Frequencies

d3-01

Jump Frequency 1
Jump Freq 1

These parameters allow programming of up to three prohibited
frequency points for eliminating problems with resonant vibration
of the motor / machine. This feature does not actually eliminate the
selected frequency values, but will accelerate and decelerate the
motor through the prohibited bandwidth.

0.0 to 200.0

0.0Hz

Programming

d3-02

Jump Frequency 2
Jump Freq 2

0.0Hz

Programming

d3-03

Jump Frequency 3
Jump Freq 3

0.0Hz

Programming

d3-04

Jump Frequency Width
Jump Bandwidth

This parameter determines the width of the deadband around each
selected prohibited frequency point. A setting of “1.0” will result in
a deadband of +/- 1.0 Hz.

0.0 to 20.0

1.0Hz

Programming

Denotes that parameter can be changed when the drive is running.

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

Advertising