Physical Installation 1 - 14

Installation Orientation and Clearances

Install the Drive vertically so as not to reduce the cooling efficiency. When installing the Drive, always provide the following
installation clearances to allow normal heat dissipation. Ensure that the heatsink is against a closed surface to avoid diverting
cooling air around the heatsink.

Fig 1.8 Drive Installation Orientation and Clearance

IMPORTANT

1. The same clearance is required horizontally and vertically for both Open Chassis (IP00) and NEMA

Type 1 Drives.

2. Always remove the top and bottom protection covers before installing a CIMR-P7U2018/4018 and

smaller Drive in a panel.
Always provide enough clearance for lifting eye bolts and the main circuit wiring when installing a
CIMR-P7U2022/4030 and larger Drive in a panel.

4.75 in (120 mm. minimum)

4.75 in (120 mm. minimum)

Air

Air

Vertical Clearance

Horizontal Clearance

1.2 in

(30.5 MM.) min.

1.2 in

(30.5 mm. minimum)

1.2 in

(30.5 mm. minimum)

4.75 in (50 mm. minimum)

4.75 in (120 mm. minimum)