Physical installation 1 - 12 – Yaskawa P7 Drive User Manual User Manual

Page 22

Advertising
background image

Physical Installation 1 - 12

Table 1.4 400V Class Heat Loss Data

TYPE

CIMR-P7U

Drive

(Inverter)

Capacity

(kVA)

Rated

Output

Current

(A)

Cooling

Fin Side

(W)

Internal

Unit Side

(W)

Total

Watt
Loss

(W)

Cooling
Method

40P4

1.4

1.8

14

39

53

Self

40P7

1.6

2.1

17

41

58

Self

41P5

2.8

3.7

36

48 84

Self

42P2

4.0

5.3

59

56

115

Fan

43P7

5.8

7.6

80

68

140

Fan

44P0

6.6

8.7

90

70

160

Fan

45P5

9.5

12.5

127

81

209

Fan

47P5

13

17

193

114

307

Fan

49P0

16

21

232

158

390

Fan

4011

21

27

232

158

390

Fan

4015

26

34

296

169

465

Fan

4018

30

40

389

201

590

Fan

4022

38

50.4

420

233

653

Fan

4024

40

52

691

297

989

Fan

4030

51

67.2

691

297

989

Fan

4037

59

77

801

332

1133

Fan

4045

73

96

901

386

1287

Fan

4055

95

125

1204

478

1682

Fan

4075

120

156

1285

562

1847

Fan

4090

140

180

1614

673

2287

Fan

4110

180

240

1889

847

2736

Fan

4132

200

260

2388

1005

3393

Fan

4160

230

304

2636

1144

3936

Fan

4185

315

414

2791

1328

3964

Fan

4220

390

515

3797

1712

5509

Fan

4300

510

675

5838

2482

8319

Fan

Advertising