L4 speed command loss detection, L4 speed command loss detection -43 – Yaskawa P7 Drive User Manual User Manual

Page 127

Advertising
background image

Programming 5 - 43

L4 Speed Command Loss Detection

L4-01 Speed Agreement Detection Level

Setting Range:

0.0 to 200.0 Hz

Factory Default: 0.0 Hz

L4-02 Speed Agreement Detection Width

Setting Range:

0.0 to 20.0 Hz

Factory Default: 2.0 Hz

Parameters L4-01 and L4-02 are user specified levels for use with the Fref/Fout Agree 1, Fref/Set Agree 1, and Freq Detect 1
& 2 digital output functions. Please refer to the H2 Digital Output Parameters in the Programming Manual for more
information.

L4-05 Frequency Reference Loss Detection Selection

L4-06 Frequency Reference at Loss of Frequency Reference

Setting Range:

0.0 to 100.0% of previous speed command

Factory Default: 80.0% of previous speed command

The Drive can be configured to compensate for the loss of its external speed command. An external speed command is
considered lost if it drops 90% of its value in 400mS or less.

Fig. 36 Loss of Frequency Reference Timing Diagram

To enable Frequency loss detection, set L4-05= “1: Enabled @ % of PrevRef”. If Frequency Reference Loss Detection is
enabled and the reference is lost, the Drive continues to operate at the speed commanded by parameter L4-06. When the speed
command returns, the Drive again follows the speed command.

Setting H2-01/H2-02= “C: Loss of Ref”, configures a digital output as a Frequency Reference Loss indication only when
L4-05= “1: Enabled @ % of PrevRef”.

Setting

Description

0

Disabled

1

Enabled @ % of PrevRef (factory default)

t

Frequency

Reference

Output

Frequency

t

10%

T

L4-06

100%

T = 400mS

100%

10%

TIME

Advertising