Communications d - 4, Related parameters – Yaskawa P7 Drive User Manual User Manual

Page 218

Advertising
background image

Communications D - 4

Related Parameters

#

Hex, see page A-30

Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:
1.

Monitoring operation status of the Drive

2.

Setting and reading Drive parameters

3.

Resetting faults

4.

Input multi-function commands

Table D.2 Serial Communication Related Parameters

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting Range

Factory

Setting

Chapter

Ref #

Menu

Location

b1-01

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference)
input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1

(or Terminal A2 see parameter H3-13)

2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick

Setting

b1-02

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital

operator

1: Terminal - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick

Setting

H5-01

Drive Node Address
Serial Comm Adr

Selects drive station node number (address) for
terminals R+, R-, S+, S-.*
Set H5-01 to 0 to disable Drive responses to Modbus
communications.

0 to 20 (Modbus)

0 to FF (N2)

0 to 63 (P1)

1F

#

Programming

H5-02

Communication Speed Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+
and S-*.
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud
3: 9600 Baud
4: 19200 Baud

0 to 4

3

Programming

H5-03

Communication Parity Selection
Serial Com Sel

Selects the communication parity for terminals R+,
R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

0

Programming

H5-04

Stopping Method after
Communication Error
Serial Fault Sel

Selects the stopping method when a communication
error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

Programming

H5-05

Communication Error Detection
Selection
Serial Flt Dtct

Enables or disables the communications time-out
detection function.
0: Disabled - A communications loss will NOT
cause a communications fault.
1: Enabled - If communications is lost for more than
the time specified in parameter H5-09, a communi-
cations fault will occur.

0 or 1

1

Programming

H5-06

Drive Transmit Wait Time
Transmit WaitTIM

Sets the time from when the drive receives data to
when the drive sends data.

5 to 65

5ms

Programming

H5-07

RTS Control Selection
RTS Control Sel

Enables or disables request to send (RTS) control:
0: Disabled
1: Enabled

0 or 1

1

Programming

H5-09

Communication Error
Detection Time
CE Detect Time

Determines how long communications must be lost
before a fault is annunciated. Works in conjunction
with parameters H5-05 and H5-04.

0.0 to 10.0

2.0sec

Programming

* After these parameters are changed drive power must be cycled before the changes will take effect.

IMPORTANT

An OR operation is performed between the multi-function command input from the DDC and the command
input from multi-function digital input terminals S3 to S7.