Remote reference (ref) indicator, Run indicator, Stop indicator – Yaskawa P7 Drive User Manual User Manual

Page 63

Advertising
background image

Digital Operator 3 - 5

REMOTE Reference (REF) Indicator

The status of the “REMOTE” Reference (REF) indicator is shown in Table 3.4. This indicator is always “Off” when the Drive
is in the “LOCAL” mode. When the Drive is in the “REMOTE” mode, the REF indicator status is dependent on the setting of
parameter b1-01 (Frequency Reference Selection). See Table 3.4.

Run Indicator

The status of the “RUN” indicator is shown in Table 3.5 when the Drive is in either the “LOCAL” or “REMOTE” mode.

Stop Indicator

The status of the “STOP” indicator is shown in Table 3.6 when the Drive is in either the “LOCAL” or “REMOTE” mode.

Table 3.4 REMOTE Reference (REF) Indicator

Indicator Status

Condition

On

Parameter b1-01 (Frequency Reference Selection) is set to terminal strip, communications, option
board, or pulse train as indicated below:
b1-01 =1 (Terminals)
=2 (Communications)
=3 (Option PCB)
=4 (Pulse Train)

Off

Parameter b1-01 (Frequency Reference Selection) is set to digital
operator as indicated below:
b1-01=0 (Operator)

Table 3.5 RUN Indicator

Indicator Status

Condition

On

Drive is running.

Blinking

Drive is decelerating to a stop.

Off

Drive is stopped.

Table 3.6 STOP Indicator

Indicator Status

Condition

On

Drive is decelerating to a stop or stopped.

Blinking

Drive is in a run condition but the frequency reference is less than the
minimum output frequency E1-09, or the Drive is running in “REMOTE” mode and the “STOP”
key on has been pressed.

Off

Drive is running.