H3 analog inputs, H3 analog inputs -33, Programming 5 - 33 – Yaskawa P7 Drive User Manual User Manual

Page 117

Advertising
background image

Programming 5 - 33

F6-05 Current Scaling via Communication Option PCB

A communication option card can read the Drive’s DPRAM to access the current monitor. The format of the current reading in
the DPRAM will be determined by parameter F6-05.

F6-05= “0: A Display”

Current is a decimal number corresponding to actual Amperes

F6-05= “1: 100%/8192 (Drive Rated Current)”

Current reading is a number where

8192 = 100% of Drive rated output current

H3 Analog Inputs

H3-02 Terminal A1 Gain Setting

Setting Range:

0.0 to 1000.0%

Factory Default: 100.0%

H3-03 Terminal A1 Bias Setting

Setting Range:

-100.0% to +100.0%

Factory Default: 0.0%

In order to have the Drive properly interpret an analog input, it may be necessary to apply a gain and/or a bias to the signal.
The analog inputs have a resolution of 10 bits (1024 steps). Using the factory default settings for the analog input’s gain and
bias, the 0-10Vdc or 4-20mA signal at the analog input will yield a 0-100% speed command span.

Fig. 23 Output Frequency as Commanded Via Analog Input

If a different span of analog input signal is desirable, it will be necessary to adjust the gain, the bias, or both to allow the analog
input level to generate the desired frequency command. Adjustment of the gain setting will change the speed command that is
equivalent to the maximum analog input (10Vdc or 20mA). If, for instance, the gain is increased to 200%, then 10Vdc or
20mA will be equivalent to a 200% speed command and 5 VAC or 12mA will be equivalent to a 100% Speed Command.
Since the Drive output is limited by the maximum frequency parameter (E1-04), 0-5Vdc or 4-12mA will now be equivalent to
0-100% speed command span.

Setting

Description

0

A Display (factory default)

1

100%/8192 (Drive Rated Current)

20mA

4mA

0V

10V

Gain = 100%

Bias = 0%

Ou

tp

u

t

F

req

uen

c

y

Analog Input Level