Communications D - 2

Using Modbus Communication

Serial communication can be performed with Direct Digital Controllers (DDCs) or similar devices using the Modbus protocol.

Modbus Communication Configuration

Modbus communication is configured using 1 master (PLC) and a maximum of 31 slaves. Serial communication between
master and slave is normally initiated by the master and responded to by the slaves.

The master performs serial communication with one slave at a time. Consequently, the slave address of each slave must be
initially set, so that the master can perform serial communication using that address. Slaves receiving commands from the
master perform the specified functions, and send a response back to the master.

Fig D. 1 Example of Connections between Master and Drive

Communication Specifications

The Modbus communication specifications are shown below:

Table D.1 Modbus Communication Specifications

Item

Specifications

Interface

RS-422, RS-485

Communications Cycle

Asynchronous (Start-stop synchronization)

Communications Parameters

Baud rate:

Select from 1200, 2400, 4800, 9600, and 19200 bps.

Data length:

8 bits fixed

Parity:

Select from even, odd, or none.

Stop bits:

1 bit selected

Communications Protocol

Modbus

Number of Connectable Units

31 units max.

Master

E7

E7

E7

Slaves