Electrical installation 2 - 7, Important, 3warning – Yaskawa P7 Drive User Manual User Manual

Page 35

Advertising
background image

Electrical Installation 2 - 7

4185

300/350

R/L1, S/L2, T/L3,

,

1

M8

88.5

(10.0)

300 X 2P

(152 X 2P)

600Vac

UL Approved

vinyl-sheathed

or equivalent

U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33

M8

88.5

(10.0)

300 X 2P

(152 X 2P)

3

M8

88.5

(10.0)

2/0

(67.4)

M16

867.4

(98.0)

3/0 X 2P

(85 X 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

12.4

(1.4)

14

(2.1)

4220

400/450

R/L1, S/L2, T/L3,

,

1

M8

88.5

(10.0)

500 X 2P

(253 X 2P)

U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33

M8

88.5

(10.0)

400 X 2P

(203 X 2P)

3

M8

88.5

(10.0)

2/0

(67.4)

M16

867.4

(98.0)

250 X 2P

(127 X 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M4

12.4

(1.4)

14

(2.1)

4300

500+

R/L1, S/L2, T/L3,

,

1

M8

88.5

(10.0)

700 X 2P

(355 X 2P)

U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L33

M8

88.5

(10.0)

600 X 2P

(304 X 2P)

3

M8

88.5

(10.0)

2/0

(67.4)

M8

867.4

(98.0)

400 X 2P

(203 X 2P)

r/

l

1,

s

200/

l

2

200,

s

400/

l

2

400

M16

12.4

(1.4)

14

(2.1)

* Use 75

°C copper wire or equivalent.

IMPORTANT

Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line

voltage drop is calculated as follows:

Line voltage drop (V) =

x wire resistance (

Ω/km) x wire length (m) x current (A) x 10

-3

Table 2.2 480Vac Wire Sizes and Connector Specifications

Drive Model

CIMR-P7U

Nominal

Hp

Terminal Symbol

Terminal

Screws

Clamping

Torque

lb. in.

(N•m)

Recommended

Wire Size AWG

(mm

2

)

Wire Type

3

WARNING

Prior to removing any protective cover or wiring any part of the Drive, remove all power sources, including
main input power and control circuit power. Wait a minimum of 5 minutes after power removal, before
removing any cover. The charge lamp located within the Drive should be off prior to working inside. Even if
the charge lamp is off, one must measure the AC input, output, and DC Bus potential to insure safe levels
prior to resuming work. Failure to adhere to this warning may result in personal injury or death.