Parameters A - 7

b5-20

PI Setpoint Display Scaling
Setpoint Scaling

Set display/setting Unit of b5-19.

0 to 39999

1

Programming

b5-21

PI Sleep Input Source
PI Sleep Source

Input Source Selection for Sleep function Mode.
0: SFS Input (This is near the PI Output.)
1: PI Setpoint
2: Snooze

0 to 2

1

Programming

b5-22

PI Snooze Level
Snooze Level

Sets the PI snooze function start level as a percentage of maximum
frequency (E1-04).

0 to 100

0%

Programming

b5-23

PI Snooze Delay Time
Snooze Delay Time

Sets the PI snooze function delay time in terms of seconds.

0 to 3600

0sec

Programming

b5-24

PI Snooze Deactivation Level
Wake-Up Level

When the PI feedback drops below this level, normal PI operation
starts again. Set as a percentage of maximum frequency (E1-04).

0 to 100

0%

Programming

b5-25

PI Setpoint Boost Setting
Setpoint Boost

Temporary increase of PI setpoint to create an overshoot of the
intended PI setpoint.

0 to 100

0%

Programming

b5-26

PI Maximum Boost Time
Max Boost Time

Sets a time limitation for reaching temporarily boosted PI setpoint
(intended PI setpoint + b5-25).

0 to 3600

0sec

Programming

b5-27

PI Snooze Feedback Level
Snooze Feedback

PI snooze mode will be activated when PI feedback is above this
level. Set as a percentage of maximum frequency (E1-04).

0 to 100

60%

Programming

b5-28

PI Feedback Square Root
Function Selection
PI Feedback SqRt

0: Disabled
1: Enabled

0 or 1

0

Programming

b5-29

PI Square Root Gain
PI Fb SqRt Gain

A multiplier applied to the square root of the feedback.

0.00 to 2.00

1.00

Programming

b5-30

Output Square Root
Monitor Selection
PI Out Moni SqRt

0: Disabled
1: Enabled

0 or 1

0

Programming

b5-31

PI Unit Selection
PI Unit Sel

Sets units for b5-19, U1-24, U1-38.
0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFahrenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic M/Hr
6: LPH:Liters/Hr
7: LPS:Liters/Sec
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Mtr:Meters

0 to 11

0

Quick

Setting*

Energy Saving

b8-01

Energy Saving Control
Selection
Energy Save Sel

Energy Savings function enable/disable selection
0: Disabled
1: Enabled

0 or 1

0

Quick Setting

b8-04

Energy Saving Coefficient
Value
Energy Save COEF

Used to fine-tune the energy savings function.

0.0 to

655.00

kVA

Dependent

Programming

b8-05

Power Detection Filter Time
kW Filter Time

0 to 2000

20ms

Programming

b8-06

Search Operation Voltage
Limit
Search V Limit

0 to 100

0%

Programming

Denotes that parameter can be changed when the drive is running. * Menu location is Programming when PI is disabled and Quick Setting when PI is enabled.

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location