Electrical Installation 2 - 20

Adjustments

7. All Drives: Program Parameter L3-04 to “0” or “3” to disable stall prevention during deceleration.

8. Heat Sink Mount Resistor Only: Program L8-01 to “1” to enable overheat protection for heat sink mount braking

resistor.

Operation Check

9. During dynamic braking, verify that the “BRAKE” lamp inside the Braking Unit is lit. This lamp illuminates only when

dynamic braking is activating (during quick deceleration).

10. During dynamic braking, ensure that the required deceleration characteristic is obtained. If not, contact Yaskawa for

assistance.

11. Reinstall and secure covers on the Braking Transistor Units, Remote Mount Resistor Units, and the Drive.