Programming 5 - 5

To successfully operate the Drive remotely, an external run command must be received by the Drive. Parameter b1-02
specifies from where the run command will be accepted.

Although the Run Source and the Reference Source (b1-01) are normally taken from the same source (e.g. digital operator,
terminals or serial communication), this is not always the case.

To issue a run command from the digital operator: Set b1-02= “0: Operator”, and use the HAND and OFF buttons to start
and stop the Drive.

To issue the run command from the terminals: Set b1-02= “1: Terminals”, and select between 2-wire and 3-wire control
operation by doing the following:

2-Wire Control The factory default setting is for 2-wire operation. In the 2-wire configuration a closure between S1 and SN
will be interpreted as a Forward Run command by the Drive. A closure between S2 and SN will be interpreted as a Reverse
Run command. If both S1 and S2 are closed, the Drive will stop (decelerate to zero speed) and the digital operator will dis-
play an EF (external fault) alarm (Flashing).

Fig. 2 2-Wire Control

3-Wire Control When any of the multi-function digital input parameters, H1-01 through H1-05, is set to 0, terminals S1 and
S2 become Run and Stop, respectively. The multi-function digital input that was set to 0 will function as a Forward/Reverse
input for the Drive. When the Forward/Reverse input is open the Drive will run in the Forward direction and when the input is
closed, the Drive will run in the Reverse direction.

In 3-wire operation a momentary closure (> 50mS) of S1 will cause the Drive to run provided that S2 is held closed. The Drive
will stop anytime the S2-SN connection is broken. If the 3-wire configuration is implemented via a 3-wire Initialization
(A1-03= “3330: 3-Wire Initial”), then terminal S3 becomes the Forward/Reverse input.

Fig. 3 3-Wire Control

To issue a run command via serial communication

:

Set b1-02= “2: Serial Com” and connect the RS-485/422 serial commu-

nication cable to R+, R-, S+, and S- on the removable terminal block.

To issue the Run command via the L

ON

W

ORKS

® option card: Set b1-02= “3: Option PCB”, and plug a L

ON

W

ORKS

®

option

board (p/n SI/J) into the 2CN port on the Control PCB. Consult the manual supplied with the option board for instructions on
integrating the Drive into your L

ON

W

ORKS

®

System.

IMPORTANT

If b1-01= “3: Option PCB” but a L

ON

W

ORKS

®

card is not installed in 2CN, an “OPE05” operator programming

error will be displayed on the digital operator and the Drive will not run.

S1

S2

SN

FWD Run/Stop

REV Run/Stop

Stop
switch
(NC contact)

Operation
switch
(NO contact)

Run command
(run on momentary close)

Stop command
(stop on momentary open)

Forward/reverse command
(multi-function input)

Sequence input common

S3 or S5

SN