Parameters A - 22

High Slip

n3-01

High-Slip Braking Deceleration
Frequency Width
HSB Decel Width

Sets how aggressively the drive decreases the output
frequency as it stops the motor. If overvoltage (OV)
faults occur during HSB, this parameter may need to be
increased.

1 to 20

5%

Programming

n3-02

High-Slip Braking Current Limit
HSB Current Ref

Sets the maximum current to be drawn during a HSB
stop. Higher n3-02 settings will shorten motor stopping
times but cause increased motor current, and therefore
increased motor heating.

100 to 200

150%

Programming

n3-03

High-Slip Braking Dwell Time at
Stop
HSB DwelTim@ Stp

Sets the amount of time the Drive will dwell at E1-09
(Minimum Frequency). If this time is set too low, the
machine inertia can cause the motor to rotate slightly
after the HSB stop is complete and the Drive output is
shut off.

0.0 to 10.0

1.0sec

Programming

n3-04

High-Slip Braking Overload Time
HSB OL Time

Sets the time required for a HSB Overload Fault to
occur when the Drive output frequency does not change
for some reason during a HSB stop. Normally this does
not need to be adjusted.

30 to 1200

40sec

Programming

Monitor Select

o1-01

User Monitor Selection
User Monitor Sel

Selects which monitor will be displayed upon power-up
when o1-02 = 4.

6 to 53

6

Programming

o1-02

User Monitor Selection After
Power-Up
Power-On Monitor

Selects which monitor will be displayed upon
power-up.
1: Frequency Ref
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)

1 to 4

1**

Programming

o1-03

Digital Operator Display Selection
Display Scaling

0 to 39999

0

Programming

o1-05

LCD Brightness Adjustment
LCD Contrast

0 to 5

3

Programming

o1-06

User Monitor Selection Mode
Monitor Mode Sel

Selects the “U1” monitors displayed on the 4th and 5th
lines of the digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1

monitors).

1: 3 Mon Selectable (Displays U1 monitors set by o1-07

and o1-08).

0 or 1

0**

Programming

o1-07

Second Line User Monitor
Selection
2nd Monitor Sel

Sets the “U1” monitor always displayed on the 4th line
of the digital operator display. Effective only when
o1-06 = 1.

(Continued on following page)

1 to 53

2**

Programming

** Factory setting changes to “2” when b5-01=1

Table 1:

Parameter List (Continued

)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

Sets the units of the Frequency References (d1-01
through d1-17) and the Frequency Reference Monitor
(U1-01).
0: Hz
1: % (100%. = E1-04)
2 to 39: RPM. (Enter the number of motor poles.)
40 to 39999: User display

Desired set/display value is set at Max.

output frequency.

4 digit number.
The number of digits from the right

the decimal point is displayed.

Example: If “200.0 is displayed at Max. output

frequency, set “12000”.

When o1-03

≥40 (user units), the unit selected in

o1-09 will be displayed for D1-01 to D1-17, U1-01,
U1-02, and U1-20

Set Value

Description

5

LCD display becomes dark

3

Standard setting

1

LCD display becomes light