Table E.2 Recommended Fuse and Circuit Breaker Ratings per NEC (480Vac Input)

Model

CIMR-P7U

Hp

Input

Amps

*1

(Continuous

Rating)

Output

Amps

*1

(Continuous

Rating)

Fuse

Selection Criteria

Circuit Breaker

Selection Criteria

Maximum

Time-Delay

Fuse Rating (A)

Maximum

Non-Time-Delay

Fuse Rating (A)

Maximum CB

Rating (A)

40P4

0.5/0.75

2.2

1.8

4

10

15

40P7

1

2.5

2.1

4

10

15

41P5

1.5/2

4.4

3.7

8

12

15

42P2

3

6.4

5.3

10

15

15

43P7

5

9

7.6

15

20

20

44P0

-

10.4

8.7

15

30

20

45P5

7.5

15

12.5

25

30

30

47P5

10

20

17

30

30

40

49P0

15

26

21

45

50

60

4011

20

33

27

45

50

60

4015

25

40

34

60

70

80

4018

30

48

40

70

80

90

4022

-

55

50.4

80

80

100

4024

40

57

52

100

100

125

4030

50

74

67.2

100

100

125

4037

60

85

77

125

125

150

4045

75

106

96

150

150

200

4055

100

134

125

200

200

225

4075

125

172

156

250

250

300

4090

150

198

180

300

300

400

4110

200

264

240

350

350

450

4132

-

286

260

400

400

600

4160

250

334

304

450

450

700

4185

300/350

456

414

600

600

800

4220

400/450

567

515

700

700

1000

4300

500+

743

675

900

900

1200

*1 Input and Output Amps are based on the Normal Duty (ND) current rating. Consult the Specification section for details on the Heavy Duty (HD) and Normal Duty (ND) ratings.