Programming 5 - 32

E2-03 No Load Current

Setting Range:

Model Dependent (see Appendix B)

Factory Default: Model Dependent

Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper
value if the no load current is not stated on the motor nameplate.

F6 Com OPT Setup (applies only to the LonWorks option)

F6-01 Operation Selection After Communication Error

If a serial communication option board is attached to the Drive at the 2CN connector, the Drive will automatically monitor the
card for any type of communication errors. F6-01 is applicable no matter whether a run command or speed command is coming
via the option board, digital operator, or terminal input. The setting of F6-01 determines whether the communication error is
seen as a fault or an alarm. If F6-01= “3: Alarm Only”, then the fault output is not energized upon a communication error. All
other settings of F6-01 cause the fault output to energize. The setting of F6-01 does not apply to any of the embedded
communication protocols used at the RS-485/422 terminals on the removable terminal board. (See parameters H5-0X).

F6-02 Option PCB External Fault Detection Selection

F6-03 Option PCB External Fault Stopping Method

If an external fault is received from the L

ON

W

ORKS

®

or other communication option card, the settings of F6-02 and F6-03 will

determine the Drive operation in reaction to the fault signal. Parameter F6-02 will determine if the external fault is always
recognized (F6-02= “0: Always Detected”) or only recognized when the Run command is active (F6-02= “1: Detected only
during operation”).
Once the fault is recognized, parameter F6-03 will determine the operation of the Drive. If parameter F6-03 is set to anything
other then “3”, the Drive will fault and a stopping sequence is begun. If F6-03= “3: Alarm Only”, then the external fault is
treated like an alarm. Operation will continue and an EF0 fault will flash on the digital operator.

Setting

Description

0

Ramp to Stop

1

Coast to Stop (factory default)

2

Fast-Stop

3

Alarm Only

Setting

Description

0

Always Detected (factory default)

1

Detected only during operation

Setting

Description

0

Ramp to Stop

1

Coast to Stop (factory default)

2

Fast-Stop

3

Alarm Only