Electrical Installation 2 - 24

DIP Switch S1

DIP Switch S1 is described in this section. The functions of DIP switch S1 are shown in Table 2.12.

Fig 2.10 DIP Switch S1 Location

Table 2.12 DIP Switch S1

Name

Function

Setting

S1-1

RS-485 and RS-422 terminating resistance

OFF: No terminating resistance
ON: Terminating resistance of 110

Ω

Factory Default = OFF

S1-2

Input method for analog input A2

OFF: 0-10 Vdc (internal resistance: 20K

Ω)

ON: 4-20mA (internal resistance: 250

Ω)

Factory Default = ON

S1

O

1

Terminating
resistance

DIP Switch S1 located on
terminal board.

2

1