Parameters a - 13 – Yaskawa P7 Drive User Manual User Manual

Page 187

Advertising
background image

Parameters A - 13

H1-03

Terminal S5 Function
Selection
Terminal S5 Sel

12: Forward Jog
Closed = drive runs forward at speed command entered into

parameter d1-17.

13: Reverse Jog
Closed = drive runs in reverse at speed command entered into

parameter d1-17.

14: Fault Reset
Closed = Resets the drive after the fault and the run
command have been removed.
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run com-

mand status.

17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run

command status.

18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with a multi-function digital output.
19: PI Disable
Turns off the PI controller, and PI setpoint becomes speed com-

mand.

1B: Program Lockout
Closed =All parameter settings can be changed.
Open = Only speed command at U1-01 can be changed.
1C: TrimCtl Increase
Closed = Increase motor speed by value in d4-02.
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as a speed

command.

Must be used in conjunction with Trim Ctrl Decrease.
1D: Trim Ctl Decrease
Closed = Decrease motor speed by value in d4-02
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as speed command.
Must be used in conjunction with Trim Ctrl Increase.

(Continued on following page)

0 to 6E

3: 2-wire
0: 3-wire

Programming

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location