Parameters a - 4, Sequence, Table 1: parameter list (continued) – Yaskawa P7 Drive User Manual User Manual

Page 178

Advertising
background image

Parameters A - 4

Sequence

b1-01

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see

parameter H3-13)

2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick Setting

b1-02

Run Command Selection
Run Source

Selects the run command input source.
0: Operator - “Run” and “Stop” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 to 3

1

Quick Setting

b1-03

Stopping Method Selection
Stopping Method

Selects the stopping method when the run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if input before

the time in C1-02 expires.)

0 to 3

0

Quick Setting

b1-04

Reverse Operation Selection
Reverse Oper

Determines the forward rotation of the motor, and if reverse opera-
tion is disabled.
0: Reverse Enabled
1: Reverse Disabled
2: Exchange Phase - Change direction of forward motor rotation.
3: ExchgPhs, Rev Dsbl - Change direction of forward motor

rotation and disable reverse operation.

0 to 3

1

Programming

b1-07

Local/Remote Run Selection
LOC/REM RUN Sel

0: Cycle Extern RUN - If the run command is closed when

switching from hand(local) mode to auto(remote) mode, the
drive will not run.

1: Accept Extrn RUN - If the run command is closed when

switching from hand(local) mode to auto(remote) mode, the
drive WILL run.

0 or 1

0

Programming

b1-08

Run Command Selection
During Program
RUN CMD at PRG

0: Disabled - Run command accepted only in the operation menu.
1: Enabled - Run command accepted in all menus

(except when b1-02 = 0).

0 or 1

0

Programming

b1-11

Drive Delay Time Setting
Wait to Run Time

After a run command, drive output will start after this delay time.

0 to 600

0sec

Programming

b1-12

Hand Frequency Reference
Selection
HAND Fref Source

Selects the speed command input source in hand mode.*
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see

parameter H3-13)

0 or 1

0

Programming

b1-13

HAND/AUTO During Run
Selection
HAND/AUTO @Run

Selects if drive will permit switching between HAND and AUTO
modes while running.
0: Disabled
1: Enabled

0 or 1

0

Programming

b1-14

Emergency Override Speed
E Override Speed

Sets the speed command used in emergency override mode when
b1-15=0.

0.00 to

120.00 Hz

0.00

Programming

b1-15

Emergency Override
Reference Selection
E OverrideRefSel

Selects the emergency override reverse source.
0: Use b1-14 Ref
1: Use AUTO Ref

0 or 1

0

Programming

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location