Programming 5 - 42

The following figure demonstrates acceleration when L3-04= “1 General Purpose”.

Fig. 34 Time Chart for Stall Prevention During Deceleration

L3-05 Stall Prevention Selection During Running

L3-06 Stall Prevention Level During Running

Setting Range:

30 to 200% of Drive rated output current

Factory Default: 120% of Drive rated output current

The Stall Prevention During Running function will attempt to avoid a Drive OC fault occurrence while the Drive is operating
at a constant speed. If L3-05= “0: Disabled”, the Drive may fault if the load increases sufficiently to cause the output current to
reach the OC fault level (180% of Drive rated output current).

If L3-05= “1: Decel Time 1”, the Drive is outputting a constant speed, and the Drive’s output current level exceeds the level set
by parameter L3-06 for more than 100 ms the Drive will begin to decelerate at the rate specified by parameter C1-02. The
Drive will continue to decelerate until the output current level drops below the L3-06 level (less a 2% hysteresis). Once the
output current drops below the L3-06 – 2% level the Drive will begin to accelerate at the currently active acceleration rate
(either C1-01 or C1-03).

If L3-05= “2: Decel Time 2”, the Drive will function as described above except C1-04 will be used instead of C1-02 as the
deceleration rate used when the output current exceeds L3-06 for more than 100 ms.

The following figure demonstrates acceleration when L3-05

≠0.

Fig. 35 Time Chart for Stall Prevention Level During Running

The L3-06 parameter is set as a percentage of the Drive rated output current. If the Drive still faults when L3-05

≠0, then either

lower the L3-06 or adjust the C1-02 or C1-04 settings for a quicker deceleration.

Setting

Description

0

Disabled

1

Decel Time 1 (factory default)

2

Decel Time 2

t

a

380/660/760 Vdc

t

Output

Frequency

DC Bus
Voltage

b

a - Set decel time
b - Decel time is extended

TIME

a

L3-06

t

Output

Frequency

Output

Current

b

a

- Decel time

C1-02 or C1-04.

b

– Active accel time

t

b

a

a - Decel time

C1-02 or C1-04

b - Active Accel time

TIME