Programming 5 - 51

o1-02 Power-On Monitor

When the Drive is powered up, three monitors are displayed on the digital operator. The first and largest monitor is the
“Power-On” monitor. The factory default “Power-On monitor” is Speed Command (U1-01). Below the Speed Command
monitor are the next two sequential monitors, Output Frequency (U1-02) and Output Current (U1-03). Pressing the
INCREASE key once scrolls the monitors to show the User Monitor as selected by o1-01. The factory default for o1-01 is the
Output Voltage monitor (U1-06).

The active monitor displayed when the Drive is powered on can be changed to either be U1-01 (Speed Command), U1-02
(Output Frequency), U1-03 (Output Current), or the User Monitor. Whichever monitor is selected as the Power-On top moni-
tor, the two monitors displayed below it are the next two sequential monitors. See example below.

For example, if the Drive needs to display the Elapsed Timer as the Power-On monitor, then o1-01 must be set to “13” and
o1-02 must be set to “4”. The next time Drive power is cycled, the digital operator displays U1-13 (Elapsed Time), U1-14
(Flash ID), and U1-15 (Term AI Level).

Setting

Description

1

Frequency Reference (factory default)

2

Output Frequency

3

Output Current

4

User Monitor (set by o1-01)

-DRIVE- Rdy

Frequency Ref

U1-

01

= 60.00Hz

- - - - - - - - - - - - - - - - - - - - - - - - - - - - -

U1-02= 60.00Hz

U1-03= 10.05A

Active Monitor

Next two
sequential
monitors

Active Monitor Title

Output Frequency

Output Current

-DRIVE- Rdy

Elapsed Time

U1-13= 2

H

- - - - - - - - - - - - - - - - - - - - - - - - - - - - -

U1-14= 03010

U1-16= 51.2%

Active Monitor

Active Monitor Title

Next two
sequential
monitors

Flash ID
Term AI Level

15