Parameters a - 15, Digital outputs, Table 1: user parameter list (continued) – Yaskawa P7 Drive User Manual User Manual

Page 189

Advertising
background image

Parameters A - 15

Table 1: User Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Digital Outputs

H2-01

Terminal M1-M2 Function
Selection
Term M1-M2 Sel

0: During RUN 1 = Closed when a run command is input or

the drive is outputting voltage.

1: Zero Speed = Closed when drive output frequency is less

than Fmin (E1-09)

2: Fref/Fout Agree 1 = Closed when drive output speed

equals the speed command within the

bandwidth of L4-02.
3: Fref/Set Agree 1 = Closed when the drive output speed

and the speed command are equal to

the value in L4-01 within the bandwidth of L4-02.
4: Freq Detect 1 = Closed when the drive output speed is

less than or equal to the value in L4-01,

with hysteresis determined by L4-02.
5: Freq Detect 2 = Closed when the drive output speed is

greater than or equal to the value in

L4-01, with hysteresis determined by L4-02.
6: Inverter Ready = Closed when the drive is not in a fault

state, and not in program mode.

7: DC Bus Undervolt = Closed when the DC bus voltage

falls below the UV trip level (L2-05)

8: Base Blk 1 = Closed when the drive is not outputting

voltage.

9: Operator Reference = Closed when the speed command

is coming from the digital operator.

A: Remote/Auto Oper = Closed when the run command is

coming from the digital operator.

B: Trq Det 1 N.O. - Closes when the output current exceeds

the value set in parameter

L6-02 for more time than is set in parameter L6-03.
C: Loss of Ref - Closes when the drive has detected a loss

of analog speed command.

Speed command is considered lost when it drops 90% in

0.4 seconds.

Parameter L4-05 determines drive reaction to a loss of

speed command.

D: DB Overheat
E: Fault - Closes when the drive experiences a major fault.
F: Not Used
10: Minor Fault - Closes when drive experiences a minor

fault or alarm.

11: Reset Cmd Active - Closes when the drive receives a

reset command from terminals or serial comms.

12: Timer Output - Output for independent timer, controlled

by b4-01 and b4-02.

Used in conjunction with a multi-function digital input.
17: Trq. Det 1 N.C. - Opens when the output current

exceeds the value set in parameter

L6-02 for more time than is set in parameter L6-03.
1A: Reverse Dir - Closes when the drive is running in the

reverse direction.

1E: Restart Enabled - Closes when the drive is performing

an automatic restart.

Automatic restart is configured by parameter L5-01.
1F: Overload (OL1) - Closes before a motor overload

occurs. (90% of OL1 time)

20: OH Prealarm - Closes when the Drive’s heatsink

temperature exceeds the setting

of parameter L8-02.
38: Drive Enable - Closes when the drive enable input is

active.

39: Waiting to Run - Closes during the time after a run

command is issued, but the Drive is not running due to
the time set in parameter b1-10.

3A: OH Freq Reduce
3B: Run Src Com/Opt
3D: Cooling Fan Err = Closed during internal cooling fan

failure

0 to 3B

0

Programming

H2-02

Terminal M3-M4 Function
Selection
Term M3-M4 Sel

0 to 3B

A

Programming