Programming 5 - 47 – Yaskawa P7 Drive User Manual User Manual

Page 131

Advertising
background image

Programming 5 - 47

After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by
the output current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least
the Torque Detection Time (L6-03), then the Torque Detection Function will change the state of any digital output configured
for Torque Detection (H2-01/H2-02= “B: Trq Det 1 N.O.”, or “17: Trq Det 1 N.C.”).

Fig. 38 Over Torque Detection

Fig. 39 Under Torque Detection