Diagnostic & troubleshooting 6 - 10 – Yaskawa P7 Drive User Manual User Manual

Page 154

Advertising
background image

Diagnostic & Troubleshooting 6 - 10

OV

DC Bus Overvolt

(Flashing)

DC Bus Overvoltage

208-240Vac: Trip point is

≥ 400Vdc

480Vac: Trip point is

≥ 800Vdc

High input voltage at R/L1,
S/L2 and T/L3

Check the input circuit and

reduce the input power to within
specifications

Extend the time in C1-02

The deceleration time is set too
short

Power factor correction
capacitors are being used on the
input to the Drive

Remove the power factor correc-
tion capacitors

OVRD

Emergcy
Override

Emergency Override
Emergency Override is active

Forward or Reverse Emergency
Override input is closed

- - -

PRHT

Motor Preheating

Motor Preheating
Motor is preheating

Motor Preheat 2 input is closed

- - -

UL3

Undertorq Det 1

(Flashing)

Undertorque Detection 1
Drive output current < L6-02 for more than
the time set in L6-03

Motor is underloaded

Ensure the values in
L6-02 and L6-03 are appropriate

Check application/machine status
to eliminate fault

UV

DC Bus Undervolt

(Flashing)

DC Bus Undervoltage

The DC bus voltage is

≤ L2-05

208-240Vac: Trip point is

≤ 190Vdc

480Vac: Trip point is

≤ 380Vdc

Low input voltage at R/L1, S/L2
and T/L3

Check the input circuit and
increase the input power to
within specifications

The acceleration time is set too
short

Extend the time in C1-01

Voltage fluctuation of the input
power is too large

Check the input voltage

UV2

CTL PS Undervolt

Control Power Supply Undervoltage of the
control circuit when running

External load connected pulling
down the Drive power supplies

Cycle power off and on to the
Drive

Repair or replace the Power PCB/
Gate Drive PCB

UV3

MC Answerback

Soft Charge Circuit Fault
The pre-charge contactor opened while the
Drive was running

Contacts on the soft charge
contactor are dirty and the soft
charge contactor does not
function mechanically

Cycle power off and on to the
Drive

Check the condition of the soft
charge contactor

Table 6.2 Alarm Displays and Processing

Digital

Operator Display

Description

Cause

Corrective Action

Advertising