Parameters a - 6, Pi control, Table 1: parameter list (continued) – Yaskawa P7 Drive User Manual User Manual

Page 180

Advertising
background image

Parameters A - 6

PI Control

b5-01

PI Mode Setting
PI Mode

This parameter enables / disables the closed loop (PI) controller.
0: Disabled
1: Enabled (commanded speed becomes PI setpoint)
3: Fref+PI

0, 1, 3

0

Quick Setting

b5-02

Proportional Gain Setting
P Gain

Sets the proportional gain of the PI controller.

0.00 to

25.00

2.00

Quick

Setting*

b5-03

Integral Time Setting
PI I Time

Sets the integral time for the PI controller. A setting of zero dis-
ables integral control.

0.0 to 360.0

5.0sec

Quick

Setting*

b5-04

Integral Limit Setting
PI I Limit

Sets the maximum output possible from the integrator. Set as a %
of fmax.

0.0 to
100.0

100%

Programming

b5-06

PI Output Limit
PI Limit

Sets the maximum output possible from the entire PI controller. Set
as a % of fmax.

0.00 to

100.0

100.0%

Programming

b5-07

PI Offset Adjustment
PI Offset

Sets the amount of offset of the output of the PI controller. Set as a
% of fmax.

The PI Offset Adjustment parameter has two different uses. Param-
eter b5-07 serves different functions depending on whether it is
used on a standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of

the PI function in a non-Differential PI loop. Every time the PI
output is updated, the offset is summed with the PI output. This
can be used to artificially kick-start a slow starting PI loop.

2: If the Drive is configured for Differential PI Regulation

(H3-09=16), then the PI Offset is the targeted maintained differ-
ential between the signal measured on analog input A1 and the
signal measured on analog input A2.

–100.0 to

+100.0

0.0%

Programming

b5-08

PI Primary Delay Time
Constant
PI Delay Time

Sets the amount of time for a filter on the output of the PI
controller.

0.00 to

10.00

0.00sec

Programming

b5-09

PI Output Level Selection
Output Level Sel

Determines whether the PI controller will be direct or reverse
acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)

0 or 1

0

Programming

b5-10

PI Output Gain Setting
Output Gain

Sets the output gain of the PI controller.

0.0 to 25.0

1.0

Programming

b5-11

PI Output Reverse Selection
Output Rev Sel

0: 0 limit (when PI output goes negative Drive stops)
1: Reverse (when PI goes negative Drive reverses)
0 limit automatic when reverse prohibit is selected using b1-04

0 or 1

0

Programming

b5-12

PI Feedback Reference
Missing Detection Selection
Fb los Det Sel

0: Disabled
1: Alarm
2: Fault

0 to 2

0

Programming

b5-13

PI Feedback Loss Detection
Level
Fb los Det Lvl

Sets the PI feedback loss detection level as a percentage of
maximum frequency (E1-04).

0 to 100

0%

Programming

b5-14

PI Feedback Loss Detection
Time
Fb los Det Time

Sets the PI feedback loss detection delay time in terms of seconds.

0.0 to 25.5

1.0sec

Programming

b5-15

Sleep Function Start
Level
Sleep Level

Sets the sleep function start frequency.

0.0 to 200.0

0.0Hz

Programming

b5-16

Sleep Delay Time
Sleep Time

Sets the sleep function delay time in terms of seconds.

0.0 to 25.5

0.0sec

Programming

b5-17

PI Accel/Decel Time
PI Acc/Dec Time

Applies an accel/decel time to the PI setpoint reference.

0.0 to 25.5

0.0sec

Programming

b5-18

PI Setpoint Selection
PI Setpoint Sel

0: Disabled
1: Enabled

0 or 1

0

Programming

b5-19

PI Setpoint Value
PI Setpoint

Depends on b5-20.

(Continued on following page)

0.00 to
100.00

0.00%

Programming

Denotes that parameter can be changed when the drive is running. * Menu location is Quick Setting when b5-01=1, and Programming when b5-01=0.

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location