5.2 Command Related Parameters Details

5-17

5

Command Related Parameters

[Setting Parameters]

[Application Notes]

1. The minimum interval between latch signals is 500 µs. An interval between latch signals that is longer than

the communications cycle is required to continuously obtain latched position data.

2. If two latch signals are input without allowing the minimum required interval, only the first latch signal

input position will be latched. The second latch signal will be ignored.

3. Use a subcommand to monitor completion status of continuous latch count, etc.
4. The parameters Pn850 to Pn853 can be changed only while the continuous latch operation is stopped.

Parameter

Name

Data

Size

(byte)

Setting Range

Unit

Factory

Setting

No.

Digit

Pn850

Latch Sequence Number

2

0 to 8

0

Pn851

Continuous Latch Count

2

0 to 255

0

Pn852

Latch Sequence Signal 1 to 4 Setting

2

0000H to 3333H

0000H

0

Latch sequence 1 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

1

Latch sequence 2 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

2

Latch sequence 3 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

3

Latch sequence 4 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

Pn853

Latch Sequence Signal 5 to 8 Setting

2

0000H to 3333H

0000H

0

Latch sequence 5 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

1

Latch sequence 6 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

2

Latch sequence 7 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal

3

Latch sequence 8 signal
selection

0

Phase C

0 to 3

0

1

EXT1 signal

2

EXT2 signal

3

EXT3 signal