2.2 Operation Sequence for Managing Parameters Using a Controller

2-9

2

Operation Sequence

2.2 Operation Sequence for Managing Parameters Using a

Controller

When the parameters are managed by a controller, the parameters are automatically transmitted from the con-

troller to the SERVOPACK when the power is turned ON. Therefore, the settings of SERVOPACK do not
need to be changed when the SERVOPACK is replaced.

∗ If the connection cannot be released normally, send DISCONNECT command for 2 or more communications cycles,

and then send CONNECT command.

Procedure

Operation

Command to Send

1

Turn on the control and main circuit power supplies.

NOP

2

Reset the previous communications status.

DISCONNECT

*

3

Establish communications connection and starts WDT count.

CONNECT

4

Check information such as device ID.

ID_RD

5

Get device setting data such as parameters.

PRM_RD, ADJ

6

Set the parameters required for device.

PRM_WR

7

Enable the parameter settings (Setup).

CONFIG

8

Turn the encoder power supply to the position data.

SENS_ON

9

Turn the servo on.

SV_ON

10

Start operation.

11

Turn the servo off.

SV_OFF

12

Disconnect the communications connection.

DISCONNECT

13

Turn the control and main circuit power supplies.