7 Data Field

7.1.5 IO Monitor Field Specifications: IO_MON

7-8

7.1.5 IO Monitor Field Specifications: IO_MON

The IO monitor field is used to monitor the I/O signal status of the SERVOPACK.

„

Applicable Commands

SMON, SV_ON, SV_OFF, SV_CTRL, FEED, HOLD, INTERPOLATE, POSING, LATCH, EX_POSING,
ZRET, VELCTRL, TRQCTRL, SENS_ON, SENS_OFF, BRK_ON, BRK_OFF, LTMOD_ON, LTMOD_OFF

I/O signal allocation is shown below.

Note: The EXT2, EXT3, and HWBB cannot be used with DC power input

Σ-V series SERVOPACKs (SGDV-†††E11).

D7

D6

D5

D4

D3

D2

D1

D0

EXT2

EXT1

PC

PB

PA

DEC

N_OT

P_OT

D15

D14

D13

D12

D11

D10

D09

D08

IO15

IO14

IO13

IO12

HBB

BRK

EXT3

Bit

Name

Contents

Value

Status

D0

P_OT

Forward run prohibited input

0

OFF

1

ON

D1

N_OT

Reverse run prohibited input

0

OFF

1

ON

D2

DEC

Homing deceleration LS input

0

OFF

1

ON

D3

PA

Encoder phase A input

0

OFF

1

ON

D4

PB

Encoder phase B input

0

OFF

1

ON

D5

PC

Encoder phase C input

0

OFF

1

ON

D6

EXT1

First external latch signal input

0

OFF

1

ON

D7

EXT2

Second external latch signal input

0

OFF

1

ON

D8

EXT3

Third external latch signal input

0

OFF

1

ON

D9

BRK

Brake output

0

Released

1

Locked

D10

HBB

Stop signal input, OR of HWBB1 signal and HWBB2 sig-
nal

0

OFF

(Forced stop released)

1

ON

(Forced stop)

D11

Reserved

0

D12

IO12

CN1 input signal selected in Pn81E.0

0

OFF (open)

1

ON (closed)

D13

IO13

CN1 input signal selected in Pn81E.1

0

OFF (open)

1

ON (closed)

D14

IO14

CN1 input signal selected in Pn81E.2

0

OFF (open)

1

ON (closed)

D15

IO15

CN1 input signal selected in Pn81E.3

0

OFF (open)

1

ON (closed)